PCF202 พีแอลซี PLC FX3SA-14MT-CM

฿5,980.00

สั่งจองสินค้าได้

คำอธิบาย

โปรแกรมเมเบิลลอจิกคอลโทรลเลอร์ Programmable Logic Control FX3SA is applicable to all kinds of fields of small scale equipment which need to simulate the quantity and function of MODBUS and Ethernet.

Specification

  • PLC FX3SA-MT-CM Transistor output (Sink) Type Made in China
  • Power Supply AC 100-240V
  • Power Consumption (W) 19W
  • 8 Digital Input  Type Sink/Source X0-X7
  • 6 Transistor Output
  • DC24V Output
  • Internal memory 16,000 steps EEPROM (program capacity is limited to 4,000 steps.)
  • High-speed counter 1-phase
      • 60 kHz : 2 points
      • 10 kHz : 4 points
  • High-speed pulse output Up to 2 axes (100 kHz)
  • Positioning control (transistor output type) 2 axes 100 kHz
  • Communication port
    • Mini USB Port Built-in (MINI B)
    • RS422 Port Directly connected GOT
  • Variable analog potentiometer 2 points
  • Interface Expansion Module fx series ( I/O ) Supports temperature and analog functions!
  • Interface RS422, FX3U-422-BD, FX3U-232-BD, ANALOG Input (FX2N-xxxxAD), ANALOG OUTPUT FX2N-xxxxDA), RS485 NN NETWORK, (FX3U-485BD), RS485 (FX3U-485BD)
  • Programming Software  GX-Developer, GX-work2

Peripheral device connecting connector (RS-422)

Communication cable

 

Dimension

  • WxHxL = 60x90x75mm

Hardware manual

Examples of input wiring [AC power type]

1. Sink input type                                               2. Source input type

 

External wiring of transistor output

Response time

  • OFF >> ON, Y000, Y001 = 5us or less/10 mA or more (5 to 24 VDC)
  • ON >> OFF, Y002 to Y015 = 0.2ms or less/200mA or more (at 24 VDC)

PROGRAMMING MANUAL

Positioning Control Instruction Description

  • DSZR ( DOG Search Zero Return) Mechanical zero return instruction with DOG search function.
  • ABS (Absolute Current Value Read) Instruction to read the current value from our servo amplifier with absolute position (ABS) detecting function.
  • DRVI (Variable Speed Pulse Output) Positioning (relative positioning) to specify the movement from the current position.
  • DRVA (Drive to Increment) Positioning (absolute positioning) to specify the target position based on the current value 0.
  • PLSV (Drive to Absolute) Instruction to change the pulse train output frequency

Example of external wiring  Transistor output (Sink)

 